Page 7 - F12-BPS-YZ102-Installation-Manual
P. 7

Mounting Set Up



                       Unit Mounting Instructions                               Unit Tubing Instructions

            1.  Carefully read “Protected Enclosure Criteria” on page 3   1.  Carefully read “Protected Enclosure Criteria” on page 3
               and “Enclosure Connection Requirements” on page 4       and “Enclosure Connection Requirements” on page 4
               before proceeding.                                      before proceeding.
            2.  Determine the Mounting configuration for the purge unit.   2.  The following instructions are for Units mounted external
               See “Typical Mounting Configurations.”                  to the Protected Enclosure. Consult factory for units
            3.  Firmly secure the unit mounting flange, if utilized, to the   which are mounted inside or through the face of the
               unit face plate using the hardware provided.            Protected Enclosure.
            4.  Drill  and  ream  four  mounting  holes  in  the  protected   3.  Connect 1” Protective Gas Supply Header to Unit Supply
               enclosure.  (see  page  6  for  unit  mounting  flange   Connection using 1/4” .035 welded or seamless wall
               dimensions and unit layout)                             stainless steel, fully reamed tubing. Protective Gas
            5.  Based on “Enclosure Connection Requirements” on page   Supply tubing should not exceed 15 feet length and 5
               4, drill and ream a 29/64” hole in protected enclosure,   bends.
               install 1/4” Enclosure Supply Bulkhead fitting. NOTE:   4.  Connect  Unit  Enclosure  Supply Connection to  the
               Protected Enclosure Supply should be installed at       Enclosure Supply bulkhead fitting using 1/4” .035 welded
               extreme opposite corner from part # PV-2 Purge Vent     or seamless wall stainless steel, fully reamed tubing.
               and 8” from the Enclosure Reference Connection.         Enclosure Supply tubing should not exceed 5 feet in
            6.  Next, drill and ream a 29/64” hole in protected enclosure,   length and 5 bends.
               install 1/4” Enclosure Reference Bulkhead fitting. NOTE:   5.  MULTIPLE  ENCLOSURE  CONNECTIONS  ONLY.
               Protected Enclosure Reference should be installed at    Connect Multiple Enclosure Protective Gas Supply Piping
               least 8” from the Enclosure Supply Connection.          (3/4” rigid pipe, fully reamed) from Protected Enclosure
            7.  Install PV-2 Purge Vent at extreme opposite corner from   #1 to Protected Enclosure #2. Repeat procedure for
               the Enclosure Supply Connection. (WARNING: The PV-2     connection between Protected Enclosure #2 and #3.
               Purge Vent is gravity operated and MUST be mounted      Protective Gas Supply piping should not exceed 10 feet
               in a true vertical position.)                           length and 5 bends between each enclosure.
            8.  Install the PV-2 Purge Vent Mounting Hub through a   6.  Connect Unit Enclosure Reference Connection to the
               1-1/4” hole on the Protected Enclosure.                 Enclosure Reference bulkhead fitting using 1/4” .035
            9.  Secure  the  Purge  Vent  from  inside  the  Protected   welded or seamless wall stainless steel, fully reamed
                                                                       tubing. Enclosure Reference tubing should not exceed
               Enclosure using the Purge Vent Mounting Nut.            20 feet length and 5 bends.
            10. Secure  Purge  Unit  Mounting  Flange  to  protected
               enclosure using hardware provided.


                                               Typical Mounting Configurations










                   Left Mount            Top Mount          Bottom Mount       Frame/Panel Mount        Right Mount


                                                 Enclosure Warning Label(s)

             Enclosure Warning Label (EWL) MUST be permanently affixed on or near all protected enclosure doors, entries and openings.
                 WARNING - PRESSURIZED ENCLOSURE                                  WARNING NOTICE
                 ENCLOSURE SHALL NOT BE OPENED UNLESS AREA IS KNOWN TO BE FREE   THIS ENCLOSURE CONTAINS HOT COMPONENTS
                 OF  FLAMMABLE  MATERIALS  OR  UNLESS A LL  DEVICES  HAVE  BEEN
                 DE-ENERGIZED. P OWER  SHALL  NOT  BE  RESTORED A FTER  ENCLOSURE   ENCLOSURE SHALL NOT BE OPENED UNLESS AREA IS KNOWN TO BE FREE
                 HAS  BEEN O PENED  UNTIL C OMBUSTIBLE  DUSTS  HAVE  BEEN  REMOVED   OF  FLAMMABLE  MATERIALS  OR  UNLESS A LL  DEVICES  HAVE  BEEN
                 AND ENCLOSURE HAS BEEN PURGED AND PRESSURIZED IN ACCORDANCE   DE-ENERGIZED FOR THE TIME SPECIFIED BELOW.
                 WITH THE UNIT START UP INSTRUCTIONS.                MINIMUM COOLONG TIME:
                                                                    BEST PURGING SYSTEMS CORPORATION     WWW.PURGEIT.COM   LA MARQUE, TEXAS USA