Page 8 - F12-BPS-YZ102-Installation-Manual
P. 8

Purge Unit Set Up



                Pressurization Unit Set Up                               Pressure Switch Set Up

     1.  Ensure Protected Enclosure Power is OFF, Enclosure   1.  The following directions are for purge models with the
        Pressure Control Valve and Purge Control Valve are      suffix -W or -B which are supplied with a flame proof
        closed and Protective Gas Supply is ON.                 differential pressure switch (DPS).
     2.  Test the Purge Vent, Model PV-2, for proper operation.
        Using the eraser end of a pencil or similar object, insert         IMPORTANT NOTE
        test object from inside the enclosure to confirm vent   The differential pressure switch is intended solely for loss
        relief ball is operating properly. Note: For side mounted,   of safe pressure alarm and should not be used to control
        Model PV-2-S, remove plug from bottom of tee fitting to   power to the protected enclosure.
        test vent relief ball operation.
     3.  Close and Seal Protected Enclosure.                2.  Connect alarm system wiring to the DPS via rigid
     4.  Slowly turn Enclosure Pressure Control Valve CCW until   conduit and seal or other approved wiring method for
        a “Safe” 0.25” w.c. reading is shown on the Enclosure   the classified location.
        Pressure Indicator. Note: Should Enclosure Pressure   3.  The DPS provides a Form C Dry NO, NC and C contact
        Control Valve require more than a quarter turn to obtain
        a “safe” enclosure pressure, carefully check all enclosure      Note: -B switches require 120V AC  or 24V DC power
        connections and doors for leakage. Seal as needed.      to operate.
     5.  Ensure a Minimum 60 psi reading on the Purge Injection   4.  The alarm system should be connected in a fail safe
        Pressure Gauge, adjust regulator if required.           configuration.
     6.  Open the Purge Control Valve fully. The Enclosure Pressure
        Gauge will go off scale to the high side, this normal.   Typical Pressure Switch Wiring Diagram
     7.  During Purge cycle, confirm minimum 60 psi reading
        on Purge Injection Pressure Gauge, adjust regulator if              C         NO         NC
        required.
     8.  Close Purge Control Valve fully. The Enclosure Pressure
        Indicator should return to a “Safe” 0.25” w.c. reading.
     9.  Calculate total protected enclosure volume (when empty).
        Determine Purge Time required (5 minutes minimum).
         Required Exchange   Time/Enclosure Volume
         4 Volumes           1 minute per 1.0 cf
         5 Volumes           1 minute per 0.8 cf                            Customer Supplied Alarm
     10. Mark purge time on Unit start up instruction name tag
        using a permanent marker.
     11.  Set up is complete. Remove any test equipment and
        proceed to Optional Enclosure Pressure Switch Set up
        if required.

                                            Cross Ventilation Diagram
     Protective                                                                                          Required
     Gas Supply                                                                                          Purge Vent
      Header
                                                       Enclosure Reference Tubing






                               Purge
                                Unit
           Unit Supply Tubing


                                                                      Protected Enclosures



     Page 8 of 14 BPS YZ102 IOM-R1.0                                             © 2018 - Best Purging Systems Corporation
   3   4   5   6   7   8   9   10   11   12   13