Page 3 - F12-BPS-YZ102-Installation-Manual
P. 3

Identifying Your Unit



                                                 Model Number Designations

                         Model # YZ-102-CI-L-U-¤                         This enclosure pressurization unit is offered in various
                                                                         styles. For proper installation and operation, examine
            Div./Zone Reduction                     Voltage*             the Unit Model Number Nameplate to identify the Unit
            Y- Div.1/Zone1 to Div. 2/Zone 2         120 VAC              Style, Area Classification and Type, as noted below.
            Z- Div.2/Zone2 to Non-Hazardous         24 VDC
            Unit Series                             OR                                     YZ103-CI-W-V
                                                                                             Purge Unit
            102- 1/4” Purge Unit                    Optimal Configuration***            Area Classification Reduction:
            Area Classification                     PM- Panel Mount                    Type Z - Cl I, Div. 2/ Zone 2, Gr.
                                                                                       C&D, to Non-hazardous
            CI- Class I Areas                       Mounting Options                   Type Y - Cl I, Div. 1/ Zone 1, Gr.
                                                                                       C&D to Div. 2/ Zone 2, Gr. C&D
            Pressure Switch Option                  U- Universal                       Purge Control for use in Hazardous
            L-  Provided Less Switch                   Mounting**                      Locations.   In  accordance w ith  the
                                                                                       National Fire Protection Association
            W- Provided With CI, Gr. C&D EXP Switch  V-  Vertical                      Standard   for   Purged   and
                                                                                       Pressurized Enclosures for Electrical
            B-  Provided With CI, Gr. B EXP Switch     Mounting                        Equipment. NFPA 496 2003.
                                                    H- Horizontal
            *  For pressure switch option “B” only     Mounting                            23HP
            **  Not Available with pressure switch options
            *** Panel Mount designed to mount through the wall of protected enclosure. U mounting only.
                                  General Information



                           Unit Specifications                               Protected Enclosure Criteria
            Purge Time:            4 Volumes @ 1 minute per 1.0 cf   The consumption of protective gas is directly related to the
                                   5 Volumes @ 1 minute per 0.8 cf   integrity of the protected enclosure plus the type of purge
            Protective Gas Supply:                Air or Inert Gas  requirements, i.e. dilution and ventilation. The following
            Gas Supply Pressure:                 80 - 125 psi max.  enclosure recommendations are provided to help minimize
            Unit Supply Connection:                1/4” tube fitting  protective gas consumption and increase purge unit efficiency.
            Enclosure Supply:                      1/4” tube fitting  1.  The enclosure should be fabricated to meet NEMA 4 or
            Enclosure Reference:                   1/4” tube fitting   12 / IP66 requirements.
            Safe Enclosure Pressure:           0.25” w.c. / 6.22 Kb  2.  Non metallic enclosures should meet ANSI/UL 94 V-O
            Safe Press. Flow Rate:            * 0.1 - 3.5 scfh per cf  or 94 5V.
            Purge Enclosure Pressure:                * 5” - 8” w.c.
            Purge Press. Flow Rate:              4 scfm @ 60 psi.   3.  Enclosure windows should be impact resistant and sized
                                                                       as small as possible.
            * Enclosure Integrity determines actual Pressure & Flow
                                                                    4.  Enclosure surface temperatures must not exceed 80%
                         Material Specifications                       of the area’s auto-ignition temperature.
                                                                    5.  Avoid obstructions and barriers which could impede
            Unit Mounting Plate:       316 Stainless Steel Brushed     protective gas flow through the protected enclosure.
            Regulator body:                  Enamel Finished Zinc
            Filter & Handle:                       Polycarbonate                Major Components List
            Enclosure Press. Gauge:           Enameled Aluminum
            Injection Press. Gauge:           Polycarbonate/Brass   Filter Regulator:
            Tubing:                            316 Stainless Steel  Enclosure Pressure Valve:
            Tube Fittings:                     316 Stainless Steel  Purge Valve:
            Valves:                            316 Stainless Steel  Purge Press. Indicator:
            Valve Handles:                         Polycarbonate    Enclosure Press. Indicator:
            Start up Labels:                   Silkscreened Lexan   Optional Pressure Loss Alarm:
            Enclosure Warning Label:               Stainless Steel  Enclosure Warning Label:                      EWL-1

                                                           WARNING
             All electrical connections of the protected enclosure and purge unit must be performed by trained and knowledgeable
             personnel. In addition, all connections must be installed in accordance with the National Electrical Code (NEC) NFPA
             70 and all relevant international, nation and local codes. The Authority Having Jurisdiction must approve all electrical
             installations. Failure to follow electrical warnings can cause harm, death or dismemberment to personnel and can cause
              damage to instrumentation.

            © 2018 - Best Purging Systems Corporation                                      BPS YZ102 IOM-R1.0  Page 3 of 14
   1   2   3   4   5   6   7   8