Page 3 - F10-BPS-YZ101B-Installation-Manual
P. 3

Identifying Your Unit



                                                 Model Number Designations

                         Model # YZ-101B-CII-L-U-¤                       This hazardous location enclosure pressurization unit
                                                                         is offered in various styles. For proper installation and
            Div./Zone Reduction                         Voltage*         operation, examine the Unit Model Number Nameplate
            Y- Div.1/Zone1 to Div. 2/Zone 2             120 VAC          to identify the Unit Style, Area Classification and Type.
            Z- Div.2/Zone2 to Non-Hazardous             24 VDC
            Unit Series                                 OR                               YZ101-CI/CII-W-V
                                                                                          Pressurization Unit
            101B- 3/8” Pressurization Unit              Optimal Configuration***        Area Classification Reduction:
            Area Classification                         PM- Panel Mount                Type Z - Cl I/II, Div. 2/ Zone 2, Gr.
                                                                                       C&D, F&G to Non-hazardous
            CII- Class II Areas                         Mounting Options               Type Y - Cl I/II, Div. 1/ Zone 1, Gr.
                                                                                       C&D, F&G to Div. 2/ Zone 2, Gr.
            Pressure Switch Option                      U- Universal                   C&D, F&G
            L-  Provided Less Switch                      Mounting**                   Purge Control for use in Hazardous
                                                                                       Locations. I n  accordance w ith  the
            W- Provided With CI, Gr. C&D EXP Switch     V-  Vertical                   National Fire Protection Association
                                                                                                  urged
                                                                                                       and
                                                                                       Standard
                                                                                              for P
            B-  Provided With CI, Gr. B EXP Switch        Mounting                     Pressurized Enclosures for Electrical
                                                        H- Horizontal                  Equipment. NFPA 496 2003.
            *  For pressure switch option “B” only        Mounting                         23HP
            **  Not Available with pressure switch options
            *** Panel Mount designed to mount through the wall of protected enclosure. U mounting only.
                                  General Information

                           Unit Specifications                               Protected Enclosure Criteria

            Protective Gas Supply:                Air or Inert Gas  The consumption of protective gas is directly related to the
            Unit Supply Pressure: w/ Purge Vent:   80 - 125 psi max.  integrity of the protected enclosure plus the type of purge
                                w/ Redundant Regulator:  5 psi max.  requirements, i.e. dilution and ventilation. The following
            Unit Supply Connection:                3/8” tube fitting  enclosure recommendations are provided to help minimize
                                                                    protective gas consumption and increase purge unit efficiency.
            Enclosure Supply:                      3/8” tube fitting  1.  The enclosure should be fabricated to meet NEMA 4 or
            Enclosure Reference:                   1/4” tube fitting   12 / IP66 requirements.
            Safe Enclosure Pressure:              0.5” w.c. / 55Kb
            Safe Press. Flow Rate:            * 0.1 - 3.5 scfh per cf  2.  Non metallic enclosures should meet ANSI/UL 94 V-O
                                                                       or 94 5V.
            Class I Purge Time:                See page 9, step 6   3.  Enclosure windows should be impact resistant and sized
            * Enclosure Integrity determines actual Flow Rate          as small as possible.
                                                                    4.  Enclosure surface temperatures must not exceed 80%
                         Material Specifications                       of the area’s auto-ignition temperature.

            Unit Mounting Plate:       316 Stainless Steel Brushed   5.  Avoid obstructions and barriers which could impede
                                                                       protective gas flow through the protected enclosure.
            Regulator body:                  Enamel Finished Zinc
            Regulator Handle:                      Polycarbonate                Major Components List
            Enclosure Press. Gauge:           Enameled Aluminum
            Tubing:                            316 Stainless Steel  Encl. Pressure Control Regulator:
            Tube Fittings:                     316 Stainless Steel  Enclosure Press. Indicator:
            Start up Labels:                   Silkscreened Lexan   Optional Pressure Loss Alarm:
            Enclosure Warning Label:               Stainless Steel  Enclosure Warning Label:                      EWL-1

                                                           WARNING
             All electrical connections of the protected enclosure and purge unit must be performed by trained and knowledgeable
             personnel. In addition, all connections must be installed in accordance with the National Electrical Code (NEC) NFPA
             70 and all relevant international, nation and local codes. The Authority Having Jurisdiction must approve all electrical
             installations. Failure to follow electrical warnings can cause harm, death or dismemberment to personnel and can cause
              damage to instrumentation.

            © 2018 - Best Purging Systems Corporation                                     BPS YZ101B IOM-R1.0 Page 3 of 14