Page 8 - F09-BPS-YZ101A-Installation-Manual
P. 8

Pressurization Unit & Switch Set Up



                Pressurization Unit Set Up                               Pressure Switch Set Up

     Class I installations require a 4 or 5 volume exchange through   1.  The following directions are for purge models with the
     the protected enclosure while maintaining a positive pressure.   suffix -W or -B which are supplied with a flame proof
     To determine unit flow rate, temporarily install a 0 - 10 scfh   differential pressure switch (DPS).
     flow meter between the unit and the protected enclosure.
     Class II installations proceed to step 1.                             IMPORTANT NOTE
     1.  Ensure Protected Enclosure Power is OFF, Enclosure   The differential pressure switch is intended solely for loss
        Pressure Control Regulator is closed and Protective   of safe pressure alarm and should not be used to control
        Gas Supply is ON.                                    power to the protected enclosure.

     2.  Adjust Redundant Regulator, if utilized, to 5 psi maximum
        or skip to step 3 if enclosure is equipped with a Model   2.  Connect alarm system wiring to the DPS via rigid
        PV-2 Purge Vent.                                        conduit and seal or other approved wiring method for
     3.  Test Purge Vent, if utilized. Using the eraser end of a   the classified location.
        pencil or similar object, insert from inside the enclosure   3.  The DPS provides a Form C Dry NO, NC and C contact.
        to confirm vent relief ball is operating properly. Note:      Note: -B switches require 120 VAC or 24 VDC power to
        Side mounted, Model PV-2-S, remove plug from bottom     operate.
        of tee fitting to test vent.
                                                            4.  The alarm system should be connected in a fail safe
     4.  Close and Seal Protected Enclosure.                    configuration.
     5.  Slowly turn Enclosure Pressure Control Regulator
        CW until a “Safe” 0.25” w.c. reading is shown on the
        Enclosure Pressure Gauge. Note: If unable to achieve a
        “ Safe” enclosure pressure, carefully check all enclosure
        connections and doors for leakage. Seal as needed.     Typical Pressure Switch Wiring Diagram
     6.  Class I, confirm and document Protective Gas flow shown            C         NO         NC
        on temporarily installed flow meter. Use formulas below
        to determine purge time required, 5 minutes minimum.
        (Total Enclosure Volume x 4)/Flow Rate
        (Total Enclosure Volume x 5)/Flow Rate
     7.  Mark purge time on Unit start up instruction name tag
        using a permanent marker.

     8.  Set up is complete. Remove any test equipment and
        proceed to Optional Enclosure Pressure Switch Set up
        if required.                                                        Customer Supplied Alarm




                                            Cross Ventilation Diagram


                                                                                                         (optional)
        Protective                                                                                      Purge Vent
       Gas Supply
         Header                                        Enclosure Reference Tubing



                                                                          Protected
                                                    Protected            Enclosure(s)
                                                   Enclosure(s)
                                Purge                                                           Protected
                                Unit                                                           Enclosure(s)
           Unit Supply Tubing







     Page 8 of 14 BPS YZ101A IOM-R1.0                                            © 2018 - Best Purging Systems Corporation
   3   4   5   6   7   8   9   10   11   12   13