Product Description                                             Model YZ101A

            Model YZ101A is a Type Y or Z pressurization unit designed to                             Type Y & Z
            protect electrical equipment in Class I and Class II Hazardous
            Areas. When connected to a supply of protective gas, the Model               Pressurization Unit
            YZ101A will supply, regulate and monitor the protective gas
            supply to a protected electrical enclosure. Type Z applications
            reduce the hazardous area rating inside the enclosure from   Class I Applications  Class II Applications
            Division 2 / Zone 2 to Unclassified. This allows general purpose
            equipment to operate in Division 2 / Zone 2 areas. Type Y   Up To 2 Cubic Feet   Up to 10 Cubic Feet
            applications reduce the hazardous area rating inside the
            enclosure from Division 1 / Zone 1 to Division 2 / Zone 2. This
            allows Division 2 / Zone 2 equipment to operate in Division 1   Technical Bulletin YZ101A TB-R0   © 07.23.2018
            / Zone 1 Hazardous Areas.
                        Unit Operation

            Prior  to  Start-Up:    Ensure  Protected  Enclosure  Power
            is OFF, Enclosure Pressure Control Regulator is closed,
            Protective Gas  Supply  is ON and alarm  system is
            activated (if utilized). If utilized, test Purge Vent for proper
            operation.  Class II  Area Start-Up: Remove all dust
            from protected enclosure. Close and seal Protected
            Enclosure. Open Enclosure Pressure Control Regulator until
            a “Safe” reading is shown on the Enclosure Pressure Gauge.
            Class I Area Start-Up: Close and seal Protected Enclosure.
            Open Enclosure Pressure Control Regulator until a “Safe”
            reading is shown on the Enclosure Pressure Gauge.  Allow unit
            to purge protected enclosure for the required time marked on
            Unit Start Up Instructions or for  5 minutes, minimum. Confirm
            protected enclosure “Safe” pressure is stable.  Energize
            protected  enclosure  equipment.  Loss  of  “Safe”  pressure
            requires immediate attention. Protected enclosure power
            should be de-energized if “Safe” pressure cannot be restored
            within a reasonable amount of time.

                     Unit Specifications

            Class I & II Maximum Enclosure Volumes:  2 &10 cubic feet
            Universal Unit Weight:                3.5 lbs.                         Universal Mount Unit
            Vertical & Horizontal Unit Weights:   8.0 & 8.0 lbs.                 less Pressure Switch for
            Operating Temp. Range:          -20° F - 120° F                     any side or panel mounting
            Protective Gas Supply:          * Air or Inert Gas
            Supply Pressure w/ RR-4 Regulator:   5 psi maximum
            Supply Pressure w/ PV-2 Vent:   80 - 125 psi maximum
            Unit Supply Connection:         1/4” tube fitting
            Enclosure Supply:               1/4” tube fitting
            Enclosure Reference:            1/4” tube fitting
            Safe Enclosure Pressure:            0.25” w.c.
            Safe Pressure Flow Rate:   ** 0.1 - 3.5 SCFH per cubic foot
            Switch Set Point on Decrease:    0.15” w.c. ± 0.02”
            Pressure Switch Conduit Port:        1/2” FPT
            Pressure Switch Contact Ratings:   See EPSK Bulletin
              *  Air must contain no more than trace amounts of flammable vapors.
              **  Enclosure integrity determines safe pressure flow rate.
               Recommended Accessories

            Redundant safety devices are necessary to protect the enclosure
            from excessive pressure of the protective gas supply in accordance
            with the requirements of NFPA 496, EN 50016 and IEC 60079-02.  Vertical Mount Unit
            Best Purging Systems Corporation therefore strongly recommends   with Pressure Switch for
            a Model RR-4 Redundant Regulator installed upstream of this unit’s   left or right side mounting
            enclosure pressure control regulator.  As an alternative, a Model
            PV-2 Spark Arresting Purge Vent may be installed on the protected                     Horizontal Mount Unit
            enclosure or the last enclosure of a pressurized enclosure array to                  with Pressure Switch for
            relieve excessive pressure created by other sources.                               top or bottom side mounting