Page 2 - BPS-RAD-Technical-Bulletin
P. 2

Specifications at a Glance                           Model Number Designations

                                                                    Typical Model Number:                  RAH - 1 - P - B
                      RAH-1
                 Class I, Division 1 Rating                         Series Model Numbers
                 Cast Aluminum Housing                              RAH  -  Remote Alarm Horn  RAB  -  Remote Alarm Beacon
                   Die Cast Zinc Grill
                  1/4”  Mounting Holes                                                   ERAB  -  Economy Remote Alarm Beacon
                   3/4” Conduit  Entry
                    8’ Pigtail Wiring                               Division Ratings
              UL & cUL Listed & CSA Certified                       1   -  Division 1      2  -  Division 2
              Class I, Division 1, Groups C & D
             Class II, Division 1, Groups E, F & G                                       COMPATIBILITY CHARTS
                                                                    Mounting Styles   RAH-1  RAH-2  RAB-1  RAB-2  ERAB-2
                                                                    C   -  Ceiling                  X      X
                      RAH-2                                         P   -  Pendant    X      *      X      X       X
                 Class I, Division 2 Rating                         W   -  Wall       *      X      X
               Die Cast Type 4X Zinc Housing                        Operating Voltages
                 with Polyurethane Finish
                  1/4”  Mounting Holes                              A    -  12-24 VDC                              X
                  (2) 3/4” Conduit  Entry                           B   -  24 VDC     X             X      X       X
                  (1) 1/2” Conduit  Entry                           C    -  120 VAC   X      X      X              X
                  Terminal Block Wiring                             D    -  240 VAC   X      X      X              X
              UL & cUL Listed & CSA Certified                       E    -  120-240 VAC                    X
            Class I, Division 2, Groups A, B ,C & D                 F    -  277 VAC                        X
              Class II, Division 2, Groups F & G
                                                                    IMPORTANT ORDERING INFORMATION:
                                                                    Use compatibility charts to determine available product options.
                      RAB-1                                         Red X designates 3-4 week availability.  All other items are 1-5 days.
                 Class I, Division 1 Rating             Optional    Consult Factory for optional dome guards and custom lens colors.
               Cast Aluminum Type 4X IP66             Model RAD-1-DG   * Suitable for Wall or Pendant Mount, but sold as listed above.
                                                       Dome Guard
                Housing with Epoxy Finish             (order seperately)
                   3/4” Conduit  Entry
                  Fresnel Glass Lens                                           Device Specifications
                  Optional Dome Guard
                 Screw Terminal Wiring
              UL & cUL Listed & CSA Certified                                          MODEL RAH-1
             Class I, Division 1 & 2, Groups C & D
             Class II, Division 1, Groups E, F & G                  Weight & Dimensions:            10.3 Lbs. / 7.625” H x  6.875” D
              Class I, Division 2, Groups A & B                     Mounting Hole Centers:                   6.5” on 45° angle
                                                                    Operating Temperature Range:               -13° F - 104° F
                                                                    Maximum Sound Level & Limitation:   100 dBa at 10 feet w/ 5 Minute Duty Cycle
                                                                    Internal Volume Control:    Featured on 120 and 240 VAC Models
                                                                    Operating Voltages:                    24 VDC @ 1.2 Amps
                                                                                                   120 VAC 50/60 Hz @ 0.20 Amps
                                                                                                   240 VAC 50/60 Hz @ 0.10 Amps
                 Pendant           Wall             Ceiling                            MODEL RAH-2
                  Mount            Mount            Mount
                                                                    Weight & Dimensions:        3.0 Lbs. / 4.53” H x  6.02” W x  3.66” D
                                                                    Operating Temperature Range:               -65° F - 150° F
                                                                    Maximum Sound Level & Options:  100 dBa at 10 feet w/ Sustained or Coded Tones
                      RAB-2                                         Operating Voltages:            120 VAC 50/60 Hz @ 0.18 Amps
                 Class I, Division 2 Rating                                                        240 VAC 50/60 Hz @ 0.09 Amps
               Cast Aluminum Type 4X IP66
                Housing with Epoxy Finish                                              MODEL RAB-1
                   3/4” Conduit  Entry                              Pendant Mount Weight & Dimensions:   15.9 Lbs / 14.54” H x  8.80” Diam.
                  Fresnel Glass Lens
                    Dome Guard                                      Wall Mount Weight & Dimensions:   19.8 Lbs. / 15.48” H x 8.80” Diam. x 14.81” W
                   24’ Pigtail Wiring                               Ceiling Mount Weight & Dimensions:   18.4 Lbs. / 14.26” H x 8.80” Diam.
               UL & cUL Listed, CSA Certified                       Operating Temperature Range:               -67° F - 150° F
            Class I, Division 2, Groups A, B, C & D                 Operating Voltages:        24 VDC @ 1.9 Amps (3.0 Amps In-rush)

                                                                                                   120 VAC 50/60 Hz @ 1.14 Amps
             Class II, Division 1, Groups E, F & G
                                                                                                   240 VAC 50/60 Hz @ 1.14 Amps
               Users may assume this device is suitable for         Flashes/Minute / Strobe Tube Life:       80 / 10,000 Hours
                 Class II, Division 2, Groups F & G  Pendant  Ceiling
                Please contact us for more information  Mount  Mount
                                                                                       MODEL RAB-2
                                                                    Weight & Dimensions:              5 Lbs. / 9.25” H x  5.5” Diam.
                     ERAB-2                                         Operating Temp. Range:                     -31° F - 104° F
                 Class I, Division 2 Rating                         Operating Voltages:       24 VDC @ 0.4 Amps (1.75 Amps In-rush)
              Aluminum Type 4X IP66 (dome up)                                          120-240 VAC @ 0.21-0.13 Amps (2.00 Amps In-rush)
               Housing w/ Polyurethane Finish                                                277 VAC @ 0.13 Amps (9.75 Amps In-rush)
                   3/4” Conduit  Entry                              Flashes/Minute / LED Lamp Life   60 or Steady-Burn  / 50,000 Hours
             Polycarbonate Dome & Fresnel Lens
                   24’ Pigtail Wiring                                                  MODEL ERAB-2
               UL & cUL Listed, CSA Certified                       Weight & Dimensions:             2 Lbs. / 7.5” H x  5.5” Diameter
            Class I, Division 2, Groups A, B, C & D                 Operating Temp. Range:                     -40° F - 104° F
              Class II, Division 2, Groups F & G                    Operating Voltages:              12-24 VDC @ 1.70-0.70 Amps
                                                                                              24 VDC @ 0.70 Amps (2.0 Amps In-rush)
              Manufacturer Installation Instructions are included                                        120 VAC @ 0.21 Amps
                                                                                                         240 VAC @ 0.13 Amps
                with all models and are available upon request!     Flashes/Minute / Strobe Tube Life:       80 / 10,000 Hours
                  IMPORTANT NOTES: All specifications subject to change without notice. Warranty & Liability policies available upon request.
            Copyright  ©  2018  -  Best  Purging  Systems  -  All  Rights  Reserved                    BPS-RAD-TB-R0                  Page  2  of  2
   1   2