Page 2 - BPS-RAD-Technical-Bulletin
P. 2
Specifications at a Glance Model Number Designations
Typical Model Number: RAH - 1 - P - B
RAH-1
Class I, Division 1 Rating Series Model Numbers
Cast Aluminum Housing RAH - Remote Alarm Horn RAB - Remote Alarm Beacon
Die Cast Zinc Grill
1/4” Mounting Holes ERAB - Economy Remote Alarm Beacon
3/4” Conduit Entry
8’ Pigtail Wiring Division Ratings
UL & cUL Listed & CSA Certified 1 - Division 1 2 - Division 2
Class I, Division 1, Groups C & D
Class II, Division 1, Groups E, F & G COMPATIBILITY CHARTS
Mounting Styles RAH-1 RAH-2 RAB-1 RAB-2 ERAB-2
C - Ceiling X X
RAH-2 P - Pendant X * X X X
Class I, Division 2 Rating W - Wall * X X
Die Cast Type 4X Zinc Housing Operating Voltages
with Polyurethane Finish
1/4” Mounting Holes A - 12-24 VDC X
(2) 3/4” Conduit Entry B - 24 VDC X X X X
(1) 1/2” Conduit Entry C - 120 VAC X X X X
Terminal Block Wiring D - 240 VAC X X X X
UL & cUL Listed & CSA Certified E - 120-240 VAC X
Class I, Division 2, Groups A, B ,C & D F - 277 VAC X
Class II, Division 2, Groups F & G
IMPORTANT ORDERING INFORMATION:
Use compatibility charts to determine available product options.
RAB-1 Red X designates 3-4 week availability. All other items are 1-5 days.
Class I, Division 1 Rating Optional Consult Factory for optional dome guards and custom lens colors.
Cast Aluminum Type 4X IP66 Model RAD-1-DG * Suitable for Wall or Pendant Mount, but sold as listed above.
Dome Guard
Housing with Epoxy Finish (order seperately)
3/4” Conduit Entry
Fresnel Glass Lens Device Specifications
Optional Dome Guard
Screw Terminal Wiring
UL & cUL Listed & CSA Certified MODEL RAH-1
Class I, Division 1 & 2, Groups C & D
Class II, Division 1, Groups E, F & G Weight & Dimensions: 10.3 Lbs. / 7.625” H x 6.875” D
Class I, Division 2, Groups A & B Mounting Hole Centers: 6.5” on 45° angle
Operating Temperature Range: -13° F - 104° F
Maximum Sound Level & Limitation: 100 dBa at 10 feet w/ 5 Minute Duty Cycle
Internal Volume Control: Featured on 120 and 240 VAC Models
Operating Voltages: 24 VDC @ 1.2 Amps
120 VAC 50/60 Hz @ 0.20 Amps
240 VAC 50/60 Hz @ 0.10 Amps
Pendant Wall Ceiling MODEL RAH-2
Mount Mount Mount
Weight & Dimensions: 3.0 Lbs. / 4.53” H x 6.02” W x 3.66” D
Operating Temperature Range: -65° F - 150° F
Maximum Sound Level & Options: 100 dBa at 10 feet w/ Sustained or Coded Tones
RAB-2 Operating Voltages: 120 VAC 50/60 Hz @ 0.18 Amps
Class I, Division 2 Rating 240 VAC 50/60 Hz @ 0.09 Amps
Cast Aluminum Type 4X IP66
Housing with Epoxy Finish MODEL RAB-1
3/4” Conduit Entry Pendant Mount Weight & Dimensions: 15.9 Lbs / 14.54” H x 8.80” Diam.
Fresnel Glass Lens
Dome Guard Wall Mount Weight & Dimensions: 19.8 Lbs. / 15.48” H x 8.80” Diam. x 14.81” W
24’ Pigtail Wiring Ceiling Mount Weight & Dimensions: 18.4 Lbs. / 14.26” H x 8.80” Diam.
UL & cUL Listed, CSA Certified Operating Temperature Range: -67° F - 150° F
Class I, Division 2, Groups A, B, C & D Operating Voltages: 24 VDC @ 1.9 Amps (3.0 Amps In-rush)
120 VAC 50/60 Hz @ 1.14 Amps
Class II, Division 1, Groups E, F & G
240 VAC 50/60 Hz @ 1.14 Amps
Users may assume this device is suitable for Flashes/Minute / Strobe Tube Life: 80 / 10,000 Hours
Class II, Division 2, Groups F & G Pendant Ceiling
Please contact us for more information Mount Mount
MODEL RAB-2
Weight & Dimensions: 5 Lbs. / 9.25” H x 5.5” Diam.
ERAB-2 Operating Temp. Range: -31° F - 104° F
Class I, Division 2 Rating Operating Voltages: 24 VDC @ 0.4 Amps (1.75 Amps In-rush)
Aluminum Type 4X IP66 (dome up) 120-240 VAC @ 0.21-0.13 Amps (2.00 Amps In-rush)
Housing w/ Polyurethane Finish 277 VAC @ 0.13 Amps (9.75 Amps In-rush)
3/4” Conduit Entry Flashes/Minute / LED Lamp Life 60 or Steady-Burn / 50,000 Hours
Polycarbonate Dome & Fresnel Lens
24’ Pigtail Wiring MODEL ERAB-2
UL & cUL Listed, CSA Certified Weight & Dimensions: 2 Lbs. / 7.5” H x 5.5” Diameter
Class I, Division 2, Groups A, B, C & D Operating Temp. Range: -40° F - 104° F
Class II, Division 2, Groups F & G Operating Voltages: 12-24 VDC @ 1.70-0.70 Amps
24 VDC @ 0.70 Amps (2.0 Amps In-rush)
Manufacturer Installation Instructions are included 120 VAC @ 0.21 Amps
240 VAC @ 0.13 Amps
with all models and are available upon request! Flashes/Minute / Strobe Tube Life: 80 / 10,000 Hours
IMPORTANT NOTES: All specifications subject to change without notice. Warranty & Liability policies available upon request.
Copyright © 2018 - Best Purging Systems - All Rights Reserved BPS-RAD-TB-R0 Page 2 of 2