Product Description                                             Model YZ101A

     Model YZ101A is a Type Y or Z pressurization unit designed to                             Type Y & Z
     protect electrical equipment in Class I and Class II Hazardous
     Areas. When connected to a supply of protective gas, the Model               Pressurization Unit
     YZ101A will supply, regulate and monitor the protective gas
     supply to a protected electrical enclosure. Type Z applications
     reduce the hazardous area rating inside the enclosure from   Class I Applications  Class II Applications
     Division 2 / Zone 2 to Unclassified. This allows general purpose
     equipment to operate in Division 2 / Zone 2 areas. Type Y   Up To 2 Cubic Feet   Up to 10 Cubic Feet
     applications reduce the hazardous area rating inside the
     enclosure from Division 1 / Zone 1 to Division 2 / Zone 2. This
     allows Division 2 / Zone 2 equipment to operate in Division 1   Technical Bulletin YZ101A TB-R0   © 07.23.2018
     / Zone 1 Hazardous Areas.
                 Unit Operation

     Prior  to  Start-Up:    Ensure  Protected  Enclosure  Power
     is OFF, Enclosure Pressure Control Regulator is closed,
     Protective Gas  Supply  is ON and alarm  system is
     activated (if utilized). If utilized, test Purge Vent for proper
     operation.  Class II  Area Start-Up: Remove all dust
     from protected enclosure. Close and seal Protected
     Enclosure. Open Enclosure Pressure Control Regulator until
     a “Safe” reading is shown on the Enclosure Pressure Gauge.
     Class I Area Start-Up: Close and seal Protected Enclosure.
     Open Enclosure Pressure Control Regulator until a “Safe”
     reading is shown on the Enclosure Pressure Gauge.  Allow unit
     to purge protected enclosure for the required time marked on
     Unit Start Up Instructions or for  5 minutes, minimum. Confirm
     protected enclosure “Safe” pressure is stable.  Energize
     protected  enclosure  equipment.  Loss  of  “Safe”  pressure
     requires immediate attention. Protected enclosure power
     should be de-energized if “Safe” pressure cannot be restored
     within a reasonable amount of time.

              Unit Specifications

     Class I & II Maximum Enclosure Volumes:  2 &10 cubic feet
     Universal Unit Weight:                3.5 lbs.                         Universal Mount Unit
     Vertical & Horizontal Unit Weights:   8.0 & 8.0 lbs.                 less Pressure Switch for
     Operating Temp. Range:          -20° F - 120° F                     any side or panel mounting
     Protective Gas Supply:          * Air or Inert Gas
     Supply Pressure w/ RR-4 Regulator:   5 psi maximum
     Supply Pressure w/ PV-2 Vent:   80 - 125 psi maximum
     Unit Supply Connection:         1/4” tube fitting
     Enclosure Supply:               1/4” tube fitting
     Enclosure Reference:            1/4” tube fitting
     Safe Enclosure Pressure:            0.25” w.c.
     Safe Pressure Flow Rate:   ** 0.1 - 3.5 SCFH per cubic foot
     Switch Set Point on Decrease:    0.15” w.c. ± 0.02”
     Pressure Switch Conduit Port:        1/2” FPT
     Pressure Switch Contact Ratings:   See EPSK Bulletin
       *  Air must contain no more than trace amounts of flammable vapors.
       **  Enclosure integrity determines safe pressure flow rate.
        Recommended Accessories

     Redundant safety devices are necessary to protect the enclosure
     from excessive pressure of the protective gas supply in accordance
     with the requirements of NFPA 496, EN 50016 and IEC 60079-02.  Vertical Mount Unit
     Best Purging Systems Corporation therefore strongly recommends   with Pressure Switch for
     a Model RR-4 Redundant Regulator installed upstream of this unit’s   left or right side mounting
     enclosure pressure control regulator.  As an alternative, a Model                     Horizontal Mount Unit
     PV-2 Spark Arresting Purge Vent may be installed on the protected
     enclosure or the last enclosure of a pressurized enclosure array to                  with Pressure Switch for
     relieve excessive pressure created by other sources.                               top or bottom side mounting