Page 10 - BEST-Type-Y-&-Z-Unit-Technical-Bulletins
P. 10

Product Description                                                Model YZ103

     Model YZ103 is a Type Y or Z pressurization unit designed                    Type Y & Z Purging
     to protect electrical equipment in Class I Hazardous Areas.
     When connected to a supply of protective gas and utilized in             & Pressurization Unit
     conjunction with a Model PV-3 Spark Arresting Purge Vent, the
     Model YZ103 will supply, regulate and monitor the protective
     gas supply to a protected electrical enclosure and accomplish   Class I Applications
     purging of the protected enclosure in an expedited manner.
     Type Z applications reduce the hazardous area rating inside the   Up To 75 Cubic Feet
     enclosure from Division 2 / Zone 2 to Unclassified. This allows
     general purpose equipment to operate in Division 2 / Zone 2
     areas. Type Y applications reduce the hazardous area rating   Technical Bulletin YZ103 TB-R0   © 07.23.2018
     inside the enclosure from Division 1 / Zone 1 to Division 2 /
     Zone 2. This allows Division 2 / Zone 2 equipment to operate
     in Division 1 / Zone 1 Hazardous Areas.

                Unit Operation

     Prior to Start-Up:  Ensure Protected Enclosure Power is
     OFF, Protective Gas Supply is ON, Filter Regulator is set to
     60 PSI, and alarm system is activated (if utilized). Test Purge
     Vent for proper operation. Start-Up: Close and seal Protected
     Enclosure. Open Enclosure Pressure Control Valve until a
     “Safe” reading is shown on the Enclosure Pressure Gauge.
     Open Purge Control Value and allow unit to purge protected
     enclosure for the required time marked on Unit Start Up
     Instructions or for  5 minutes, minimum and then close Purge
     Control Valve. Confirm protected enclosure “Safe” pressure
     is stable.  Energize protected enclosure equipment. Loss of
     “Safe” pressure requires immediate attention. De-energized
     power if “Safe” pressure cannot be restored within a reasonable
     amount of time.

           Product Specifications


     Maximum Enclosure Volume:         75 cubic feet
     Universal Unit Weight:               9.5 lbs.
     Vertical & Horizontal Unit Weights:   14.0 & 14.0 lbs.
     Operating Temp. Range:          -20° F - 120° F                       Universal Mount Unit
     Protective Gas Supply:         * Air or Inert Gas                    less Pressure Switch for
     Unit Supply Pressure:      80 - 125 psi maximum                    any side or panel mounting
     Unit Supply Connection:         3/8” tube fitting
     Enclosure Supply:               3/8” tube fitting
     Enclosure Reference:            1/4” tube fitting
     Safe Enclosure Pressure:            0.25” w.c.
     Safe Pressure Flow Rate:   ** 0.1 - 3.5 SCFH per cubic foot
     Purging Enclosure Pressure:      ** 5” - 8” w.c.
     Purging Flow Rate:   10 SCFM / 600 SCFH @ 60 psi
     4 Volume Purge Time:    1 minute per 2.5 cubic foot
     5 Volume Purge Time:    1 minute per 2.0 cubic foot
     Switch Set Point on Decrease:    0.15” w.c. ± 0.02”
     Pressure Switch Conduit Port:       1/2” FPT
     Pressure Switch Contact Ratings:   See EPSK Bulletin
       *  Air must contain no more than trace amounts of flammable vapors.
       **  Enclosure integrity determines safe pressure flow rate and
          purging enclosure pressure.

             Required Accessory

     A Model PV-3 Spark Arresting Vent is required for proper operation
     of the purging cycle and to protect the enclosure from excessive   Vertical Mount Unit
     pressure of the protective gas supply in accordance with the     with Pressure Switch for
     requirements of NFPA 496, EN 50016 and IEC 60079-02.
                                                      left or right side mounting
     Best Purging Systems Corporation therefore requires the purchase of                   Horizontal Mount Unit
     a Model PV-3 Spark Arresting Purge Vent with this unit for installation              with Pressure Switch for
     on the protected enclosure or the last enclosure of an enclosure array.             top or bottom side mounting







                                                            Copyright © 2018 - Best Purging Systems Corporation All Rights Reserved
   5   6   7   8   9   10   11   12   13   14   15