Required Accessories for ALL                                        Model EPWN &
                     Protected Enclosures
                                                                                                        ETWN


                      EPWN Nameplate
                                                              Enclosure Pressure & Enclosure Temperature
            Model EPWN Enclosure Pressurization Warning                     Warning Nameplates
            Nameplates are intended for all protected
            enclosures.  One (1) nameplate is furnished with
            all Pressurization and Purging Units, but additional   Technical Bulletin EWN TB-R0          © 07.10.2018
            nameplates must be ordered separately at time of
            order to label all doors of the protected enclosure,
            as required by NFPA 496.

            These nameplates are an essential accessory
            and required by NFPA 496 to ensure operators
            and maintenance personnel are advised that
            they must not open the protected enclosure while
            internal devices that are not suitable for use in
            the  Hazardous Area  are  energized.   To  meet
            protected enclosure labeling requirements for both
            Class I and Class II, the warning also prescribes
            that all combustible dust must be removed from
            the protected enclosure and it must be properly
            purged or pressurized after it is opened, before
            re-energizing  any  internal  devices  that  are  not
            suitable for use in the Hazardous Area.

                      ETWN Nameplate
                                                                                      Model
            Model ETWN Enclosure  Temperature Warning
            Nameplates are intended for protected enclosures                          EPWN
            that feature internal devices with surface
            temperatures that exceed the T Code Rating of
            the surrounding Hazardous  Area  atmosphere.
            These items must be ordered separately at time
            of  order  and  are  required  for  all  doors  of  the
            protected enclosure.
            They are an essential accessory and required by
            NFPA 496 to ensure operators and maintenance
            personnel are advised that they must wait for
            the established time period before opening the
            protected enclosure to prevent ignition of the
            surrounding atmosphere.   The cooling time in
            minutes  must  be  determined  by  the  user and
            inscribed on the nameplate at time of installation,
            or you may request the inscription at time of order
            if already established and known.

                        Specifications                                                Model
                                                                                      ETWN
            Dimensions:                      5” W x 2” H
            Mounting Hole Diameter:              0.125”
            Adhesive Backing:              * 3M VHB       Achieve total compliance to NFPA 496 by applying
            Material:           0.10” Anodized Aluminum
            Legends:          Silk-Screened Enamel Paint   these labels to all doors of your protected enclosure!
            * Door surfaces must be cleaned for maximum adhesion.
            All Specifications subject to change without notice.         Please contact a Sales Associate
            3M & VHB are trademarks of the 3M Corporation       for more information and customization options.